VD500 Series Inverter User Manual Parameter Description
- 157 -
Fb-20
Frequency Reached
Detection Amplitude
0.0%~100.0% (max frequency)
0.0%
○
The running frequency of the inverter, in a certain range of target frequency, inverter multi-function
DO output ON signal.
This parameter is used to set the detection range of frequency reached, which is relative to the
percentage of the maximum frequency. The diagram below is the frequency reached.
ON
ON
Time(t)
Detection
range
Set
frequency
Output
frequency(Hz)
Frequency
reaching
detection signal
Fig 6-24 Schematic diagram of frequency reached detect amplitude
Fb-21
Any Frequency Reaching
Detection Value 1
0.00Hz~max frequency
50.00Hz
○
Fb-22
Any Frequency Reaching
Detection Amplitude 1
0.0%~100.0% (max frequency)
0.0%
○
Fb-23
Any Frequency Reaching
Detection Value 2
0.00Hz~max frequency
50.00Hz
○
Fb-24
Any Frequency Reaching
Detection Amplitude 2
0.0%~100.0% (max frequency)
0.0%
○
When the output frequency of frequency converter, in the range of positive and nagetive detection
amplitude of the detection value at any time, muti-function DO output ON signal.
VD500 provides two sets of any frequency reaching detection parameters, set the frequency value
and frequency detection range respectively. The diagram below is a diagram of the function.