Parameter Description VD500 Series Inverter User Manual
- 124 -
Fig 6-14 Back and forth control mode
F5-01
DI1 Input Terminal
Function Selection
1
◎
F5-02
DI2 Input Terminal
Function Selection
2
◎
F5-03
DI3 Input Terminal
Function Selection
4
◎
F5-04
DI4 Input Terminal
Function Selection
6
◎
F5-05
DI5 Input Terminal
Function Selection
8
◎
F5-06
HdI1 Terminal Function
Selection
0
◎
F5-07
DI7 Input Terminal
Function Selection
0
◎
F5-08
DI8 Input Terminal
Function Selection
0
◎
F5-09
DI9 Input Terminal
Function Selection
0~63, see table blow
0
◎
This parameter is used to set the functions of the multifunctional digital input terminals.
Set
Value
Function
Description
0
No function
The terminals not being used can be set “no function”, to avoid
wrong operation.
1
Forward running
2
Reverse running
Via external terminals to control inverter forward reverse run
3
Three-line run
control
Via this terminal to confirm the inverter run mode is 3line run or
alternative control mode. Refer to the function code F5-00
(“terminal command mode”) description.
4
Forward
Jog(FJOG)
5
Reverse
Jog(RJOG
)
FJOG is jog forward run, RJOG is jog reverse run. Jog run
frequency, jog Acceleration/down time refer to function code
Fb-00, Fb-01, Fb-02 description.