45
DMV-100 Rotor Creep and Speed Detector - Installation Manual
15
POS-H: Position meter upper limit
(-19999 to 99999)
Press the
Shift
key to edit the parameter and use
Up
key to select
135
.
Press the
Mode
key for next parameter.
16
POS-L: Position meter lower limit
(-19999 to 99999)
Press the
Shift
key to edit the parameter and use
Up
key to select
0
.
Press the
Level
key to access the
Linear output level
set of parameters.
Linear output
= set of parameters at Level 5
17
LSET.C: Linear current model
(0 to 20 mA or 4 to 20 mA)
Press the
Shift
key to edit the parameter and use the
Up
key to select
4-
20
mA.
Press the
Mode
key for next parameter.
18
LSET.H: Linear output upper limit
(-19999 to 99999)
Press the
Shift
key to edit the parameter and use
Up
key to select
135
.
Press the
Mode
key for next parameter.
19
LSET.L: Linear output lower limit
(-19999 to 99999)
Press the
Shift
key to edit the parameter and use
Up
key to select
0
.
Press the
Level
key to access the
Output test
level.
20
This concludes the configuration.
Press and hold the
Level
key at least 3 seconds to return to the Monitor mode.