44
DMV-100 Rotor Creep and Speed Detector - Installation Manual
7
AVG-T: Average type
(Simple average / Moving Average)
Press the
Shift
key to edit the parameter and use
Up
key to select
Simple
average.
Press the
Mode
key for next parameter.
8
AVG-N: Averaging times
(1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024 times)
Press the
Shift
key to edit the parameter and use
Up
key to select
16
.
(16 = 320 ms refresh period)
Press the
Mode
key for next parameter.
9
AT.ZA: Auto-zero time A
(0.0 to 2999.9)
Press the
Shift
key to edit the parameter and use
Up
key to select
1
.
Press the
Mode
key for next parameter.
10
MEMO: Power interruption memory
(OFF, ON)
Press the
Shift
key to edit the parameter and use
Up
key to select
OFF
.
Press the
Level
key to access the
Display adjustment
parameters.
Display adjustment
= set of parameters at Level 2
11
D.REF: Display refresh period
(OFF, 0.5 s, 1s, 2s, 4s)
Press the
Shift
key to edit the parameter and use
Up
key to select
0.5
s.
Press the
Mode
key for next parameter.
12
DISP: Display value selection
(PV, MAX, MIN)
Press the
Shift
key to edit the parameter and use
Up
key to select
PV
.
Press the
Mode
key for next parameter.
13
RET: Automatic display return
(0 to 99 s)
Press the
Shift
key to edit the parameter and use the
Up
key to set the
value to
10
s.
Press the
Mode
key for next parameter.
14
POS-T: Position meter type
(OFF, incremental, incremental (reversed))
Press the
Shift
key to edit the parameter and use the
Up
key to select
inc
remental.
Press the
Mode
key for next parameter.