DMV-100 Rotor Creep and Speed Detector - Installation Manual
5.3.3 Connecting the DCC-631 Conditioner to the DMV-100 Unit
Figure 32 : Power input and signal output M12 connectorized cable connectors assignment
This connector receives the flying-lead end of the extension cable running from the DCC-631 conditioner to
the DMV-100 unit. Five conducting wires and shield must be connected as shown. The power and output
cable sends creep detection signals and 1/pole pulses to the DMV-100 rack-mount unit, while the DMV-100
rack-mount unit uses one pair to send +24VDC power to the DCC-631 conditioner.
Table 2: M12 connectorized cable to 8-position removable connector
Pin #
Standard
M12 over-molded cable
Designation
8
Brown
+24 V
DC
to DCC-631
7
Blue
Common to DCC-631
6
White
(future use)
4
Black
Creep detection from DCC-631 (24VDC when machine stopped)
2
Gray
Pulse (1/pole) from DCC-631
1
Shield
(ends at M12 connector plastic body)