M-4
07/2003
M-5
07/2003
DETAILED REFRIGERATION CYCLE
The following is a detailed refrigeration cycle as it applies to the refrigeration system
installed in Vendo equipment. (Refer to the flow chart in Figure 1.)
As the air temperature in the cabinet rises, the electronic temperature sensor reports
the air temperature to the electronic controller. The electronic controller actuates the
refrigeration control relay, which turns on both the compressor and condenser fan motor.
The evaporator fan pulls air from the front of the refrigerated space of the cabinet. It pulls
the air through the evaporator, and blows it up the rear of the vend stack. (The evaporator
fan runs continuously.) As the air passes through the evaporator, heat is drawn from the
air and transferred to the liquid refrigerant. As the cooled air circulates through the vend
stack, heat is drawn from the product and transferred to the circulating air. The heated air
is again drawn through the evaporator where the heat is removed.
In the evaporator, the liquid refrigerant draws heat from the circulating air. As refrigerant
receives heat, it vaporizes.
The compressor pumps the vapor from the evaporator and compresses it, increasing both
pressure and temperature. The compressor forces the compressed vapor out, through
the discharge line and into the condenser.
The condenser fan pulls air through the condenser. As the hot refrigerant vapor passes
through the condenser tubes, heat is drawn from the vapor. This heat is dissipated into
the passing air. The air then exits out the back of the vendor. As the refrigerant vapor in
the condenser lines is cooled, it returns to a liquid state.
From the condenser the liquid flows to the drier. The drier removes any water and solid
particles from the liquid refrigerant.
The cooled liquid refrigerant continues from the drier, through the capillary tube, to the
evaporator. The capillary tube steadies the flow rate of the refrigerant. Its small inside
diameter allows the pressure in the evaporator to remain low while the pressure in the
condenser is high.
The cool refrigerant in the evaporator draws heat from the circulating air in the cabinet.
As the temperature in the cabinet drops, the electronic temperature sensor reports the
air temperature to the electronic controller. The electronic controller deactivates the
refrigeration control relay, which turns off the compressor and condenser fan motor.
When the air temperature in the cabinet rises above the electronic controller’s cut in
setting, the compressor and the condenser fan engage again.
Summary of Contents for VARI-PAK 450
Page 2: ...TC 1 07 2003 PARTS AND SERVICE MANUAL VARI PAK...
Page 5: ...S 1 07 2003 SAFETY SECTION VARI PAK...
Page 8: ...S 4 07 2003 FIGURE 1...
Page 20: ...S 16 07 2003 NOTES...
Page 21: ...G 1 07 2003 GENERAL INFORMATION SECTION VARI PAK...
Page 28: ...G 8 07 2003 NOTES...
Page 29: ...CL 1 07 2003 CLEANING INFORMATION SECTION VARI PAK...
Page 32: ...CL 4 07 2003 NOTES...
Page 33: ...PG 1 07 2003 14 1 PROGRAMMING SECTION VARI PAK...
Page 57: ...C 1 07 2003 CABINET PARTS SECTION VARI PAK...
Page 59: ...C 3 07 2003 HARDWARE LIST...
Page 60: ...C 4 07 2003...
Page 61: ...C 5 07 2003...
Page 62: ...C 6 07 2003...
Page 64: ...C 8 07 2003...
Page 66: ...C 10 07 2003...
Page 68: ...C 12 07 2003...
Page 70: ...C 14 07 2003...
Page 72: ...C 16 07 2003...
Page 75: ...C 19 07 2003 NOTES...
Page 76: ...D 1 07 2003 DOOR PARTS SECTION VARI PAK...
Page 77: ...D 2 07 2003...
Page 79: ...D 4 07 2003...
Page 81: ...D 6 07 2003...
Page 83: ...D 8 07 2003...
Page 85: ...D 10 07 2003...
Page 87: ...D 12 07 2003...
Page 89: ...D 14 07 2003...
Page 91: ...D 16 07 2003 NOTES...
Page 92: ...M 1 07 2003 MAINTENANCE SECTION VARI PAK...
Page 98: ...M 7 07 2003 FIGURE 2...
Page 100: ...M 9 07 2003 NOTES...
Page 101: ...T 1 07 2003 TROUBLESHOOTING SECTION VARI PAK...
Page 112: ...T 12 07 2003 NOTES...