Velocity Operation Manual
www.velocitydetection.com
49
The ‘Ext. Time’ is the duration of the second time
delay and can be configured between 1-180
seconds.
To change the time, press either the + or – button
to increase or decrease the zone number.
You can also type in the number via the panel
numerical keyboard, to do this press on the zone
number field. Type in the required zone number
and press the green tick to confirm.
When finished, press the exit icon
. The panel
will ask if you want to save the changes.
Press tick
to save the changes, or press to
discard.
When an alarm from an automatic device is
received, the first delay timer will start. The alarm
will need to be acknowledged in order to start the
secondary delay timer. An acknowledged alarm
event will change from flashing red to a solid white
colour.
If the alarm is not acknowledged or reset during the
first time delay of 15 seconds, all the appropriate
outputs will be activated
If the delay needs to be overridden, then press the
icon to cancel the delay and immediately
activate the programmed outputs.
During the secondary delay timer, if the alarm is not
reset during the time delay of 180 seconds, all the
appropriate outputs will be activated.
If the delay needs to be overridden, then press the
icon to cancel the delay and immediately
activate the programmed outputs.
A second alarm indication during any of the delays,
or if a manual alarm is activated, will immediately
cause the activation of the appropriate outputs.