Velocity Operation Manual
www.velocitydetection.com
55
To re-enable a device, use the same procedure, pressing
the ‘Mode’ field until it shows ‘Enabled’.
Once a SLC device is disabled, the panel ignores any alarm or trouble generated by the device. If all devices in a zone are disabled, the
panel will indicate a zone disablement. If subsequently one or more devices in that zone are re-enabled then the zone disablement
indication will be automatically cancelled.
Alarm Group Disablement
Enter the Engineer or User Password, Press the menu
access
icon , and select the Alarm group Icon
(The disabling function is available to engineer & users).
The panel shows the Alarm Group Explorer.
Global Mode Disablement
When Global mode is set to disabled, the panel will not activate any alarm group devices.
This might be used if the system requires routine maintenance, and the user needs the rest of the system to continue running, but
doesn’t want spurious NAC activations.
The panel will respond in the usual manner to any events in any non-disabled zones.
Global mode can be disabled, but it is good practice to only disable one alarm group at a time.
Global mode can be disabled as follows:
Change the global mode for relay status to disable by
pressing the ‘Disabled’ selection area. The text will
change from ‘All enabled’ to ‘All disabled’ for relay
status.
This will disable
ALL
panel relay output interfaces.
Press the exit icon
. The panel will ask if you want to
save the changes.
Press tick
to save the changes, or press
to
discard.