SLC & Local/IO Relay Output Delays
Relay outputs can also be delayed via the cause and effect actions. In this case, no LED is lit to indicate a delay (since this type of output
is not mandatory).
Mains Fault Relay Output Delay
In the event of a mains power failure, the Velocity can be programmed to delay its TRM trouble relay for a time of between 0-240
minutes. This is normally used when operators do not require momentary mains power failures to send trouble notifications to
monitoring stations.
Go to the engineer menu, and select the Delays Icon
The panel shows the Delays screen.
See the ‘Main Delayed’ with the number input field.