Trouble:
Relay will act as a common trouble relay, and will react to ANY
trouble condition on the panel. Cannot be disabled or controlled
by cause & effects. Relay will become normally energised.
Supervisory:
Relay will act as a common supervisory relay, and will react to
ANY supervisory condition on the panel. Cannot be disabled or
controlled by cause & effects.
To change the output type, press on the + button to cycle through
the options.
When you have finished configuring the module output, you can
press the
or
arrows to change to the next output number
on the module, or press
to exit and either confirm or dismiss
the changes.