9
VFLPG/VFL/VTL/VRA
Installation
1. If the heater is not to be used within three months, store in a dry room (max. 40% RH).
2. Heater VFLPG/VFL/VTL is designed for installation in duct systems. Heater VRA is designed for installation in a
air handling unit.
3. The direction of air through the heater must follow the air flow arrow on the heater.
4. The heater may be installed in a horizontal or a vertical duct, with the junction box to the side. Installation with the
junction box above or below is NOT allowed.
5. Inlets into rooms must be covered by a fixed grill or air inlet unit that prevents the heating elements from being
touched in the case a protective grill is not installed on the heater.
6. A warning text regarding not covering the heater should be placed next to the outlet air opening.
7. The minimum distance to duct bends, dampers, filters etc. must be at least the same as the diagonal length of
the heater, i. e. the measurement from corner to corner of the heater’s duct section. Otherwise there is a risk for
irregularities in the air stream through the heater, which may trigger the overheat protection.
8. The heater may be insulated in accordance with applicable regulations for ventilation ducts/ventilation devices. The
insulation must consist of fireproof insulation material. The insulation may not cover the lid as the rating plate and
warning sign must be visible and the lid must be accessible for opening. The heater must be accessible for
replacement and inspections.
9. The distance from the heater’s metal surface to wood or other flammable material may NOT be less than 100 mm.
Maintenance
1. In normal situations there is no need for maintenance. A periodic control of functions and re-tightening of power
supply connections must be carried out at least once per year.
2. To maintain insulation in the heating element, the power stage must be connected and run for 24h at least every 3
months.
Overheating
The heater contains at least two overheating protections (of which at least one is reset manually). If the overheating
protection that is reset manually is triggered, the following must be taken into consideration:
1. Cut off the power supply.
2. The heater’s lid may only be opened by a qualified technician.
3. Thoroughly investigate the cause for the overheating protection being triggered.
4. When the fault has been rectified, the overheating protection may be reset.
Summary of Contents for MQC
Page 29: ...29 VFLPG VFL VTL VRA 1 40 2 VFLPG VFL VTL VRA 3 4 5 6 7 8 9 100 1 2 24 3 1 2 3...
Page 35: ...MQEM MQEML 35 VFLPG VFL VTL VRA...
Page 44: ...44 VFLPG VFL VTL VRA MQX MQXL MQY MQYL...
Page 48: ...48 VFLPG VFL VTL VRA MQC MQCL...
Page 53: ...53 VFLPG VFL VTL VRA MQP MQPL...
Page 54: ...54 VFLPG VFL VTL VRA...
Page 55: ...55 VFLPG VFL VTL VRA...