8
VFLPG/VFL/VTL/VRA
Safety Information
1. This appliance may be used by children aged eight years or above, people with physical and
mental disabilities as well as those who lack any experience, provided that they have received
detailed instructions about the functionality of the appliance and any risks. Children must not play
with the appliance. Cleaning and maintenance must not be performed by children without proper
supervision. Children under three years of age should not be near the appliance without constant
supervision. Children between three and eight years old may only turn on/shut off the appliance
if it is located in a suitable position and they have received instructions about the proper course of
action, or are being supervised.
They shall also be informed about possible dangers. Children between three and eight years old may
not connect the device, change its settings or perform care/maintenance.
2. All installation work must be carried out by a qualified technician.
3. The heater’s data for voltage and power is stated on the wiring diagram placed on the inside of
the cover as well as on the specification plate on the outside of the cover. The wiring diagram also
contains information regarding overheating protection.
4. The allowed ambient temperature is -20 °C ... +30°C. The heater has been designed for a maximum
allowed outgoing air temperature which is also stated on the rating plate.
5. The heater must be connected to the mains supply with a fixed cable. An all phase switch must be
included in the fixed installation. Conduit entries must be of a type that allows the heater’s ingress
protection class to be retained. The heater’s IP class is stated on the rating plate. IP55/IP65 models
are supplied with factory-installed cable glands.
6. It must not be possible to supply power to the heater without the fan previously having been turned
on. It must also be impossible to turn off the fan without interrupting the heater’s power supply.
For outputs higher than 30 kW, it is recommended that an after-blow period of at least 3 minutes is
used before the fan is stopped. This is to ensure that the overheating protection is not triggered by
the remaining heat.
7. Air speed through the heater must be at least 1.5 m/s when the outgoing temperature is max. 50°C.
8. The heater has CE marking and is produced in accordance with EN 60335–1 / EN 60335–20 /
EN 61000-6-2 / EN 61000-6-3 / EN 62233.
9. Never attempt to open the heater while it is connected to mains electricity.
10. Heaters of MQ-... type have a built-in interlocking electronic flow measuring system that ensures
that the heater output is not affected, but that there is a sufficient air flow through the heater.
Incoming air to the heater must be filtered to minimise the risk for contaminating the air measuring
system.
GB
Summary of Contents for MQC
Page 29: ...29 VFLPG VFL VTL VRA 1 40 2 VFLPG VFL VTL VRA 3 4 5 6 7 8 9 100 1 2 24 3 1 2 3...
Page 35: ...MQEM MQEML 35 VFLPG VFL VTL VRA...
Page 44: ...44 VFLPG VFL VTL VRA MQX MQXL MQY MQYL...
Page 48: ...48 VFLPG VFL VTL VRA MQC MQCL...
Page 53: ...53 VFLPG VFL VTL VRA MQP MQPL...
Page 54: ...54 VFLPG VFL VTL VRA...
Page 55: ...55 VFLPG VFL VTL VRA...