COMMISSIONING AND ADJUSTMENT 37
Name/function
Explanation
41551
W Request Fireplace
Demand State
0: Not supported
1: Not supported
2: No demand
3: Demand
42000
-W Reset Air Filter Timer
Value 0 resets filter timer
42001
RW Standby speed supply
Min : 0 %
Max : 40 %
Note: Setting Tag 61
42002
RW Standby speed exhaust
Min : 0 %
Max : 40 %
Note: Setting Tag 62
42003
RW Low speed supply
Min : 0 %
Max : 80 %
Note: Setting Tag 63
42004
RW Low speed exhaust
Min : 0 %
Max : 80 %
Note: Setting Tag 64
42005
RW Medium speed supply
Min : 0 %
Max : 100 %
Note: Setting Tag 65
42006
RW Medium speed exhaust
Min : 10 %
Max : 100 %
Note: Setting Tag 66
42007
RW High speed supply
Min : 0 %
Max : 100 %
Note: Setting Tag 67
42008
RW High speed exhaust
Min : 10%
Max : 100 %
Note: Setting Tag 68
42013 42014
RW Room temperature
heating setpoint
Min : 0 °C
Max : 30 °C
Note: Setting Tag 117
42015 42016
RW Room temperature
cooling offset
Min : 1 K
Max : 10 K
Note: Setting Tag 132
42020
RW Fireplace Demand Duration
Min: 0 Sec
Max: 60000 Sec
Note: Setting tag 238
49000
RW* Operation
0 = Read a time schedule switch point
1 = Change a time schedule switch point
49001
R-Time schedule
Operation Status
Current status of the time schedule action
0 = No action has been performed yet
1 = Configuration of time schedule is modified
(A write on register “Operation (49000)” is needed
to update the target)
2 = Configuring the time schedule on the target is
ongoing
3 = Configuring the time schedule on the target is
finished
Note: (check register 49002 to see if the change in
the time schedule was accepted by the product)
4 = RF communication problem