49010
R- Number Of Switch Points
49011
RW Index Switch Point
49012
RW Day Of Week
0 = Monday
1 = Tuesday
2 = Wednesday
3 = Thursday
4 = Friday
5 = Saturday
6 = Sunday
9Fh = Monday, Tuesday, Wednesday, Thursday, Friday
E0h = Saterday, Sunday
FFh = All days
49013
RW Hour
49014
RW Minutes
49015
RW Switch Point Control Mode
1 = Off
2 = Auto
3 = Holiday, low, middle, high, boost
49016
RW Switch Point Auto RH
0 = RH control enabled
1 = No RH control
Note: (this register is only considered when register
49015 is set to “Auto”)
49017
RW Switch Point Auto CO
2
0 = CO
2
control enabled
1 = No CO
2
control
Note: (this register is only considered when register
49015 is set to “Auto”)
49050
R-Time schedule active
0 – Time schedule is not active
1 – Time schedule is active
2 – Time schedule is active, but is changing time
schedule
Note: A read on this register starts a RF query to the
device. Read again to read the last received value.
49052
R-UI schedule type
1= 24h (Every day the same)
2 = 5-2 (Mo-Fr, Sa-Su)
3 = 7 day
49053
R-Switch Points Per Day
0 = No Fixed number of switched points per day
1 until 15
49054
R-Available UI schedule type
bit 1: 24h (Every day the same)
bit 2: 5-2 (Mo-Fr, Sa-Su)
bit 3: 7 day
49060
RW* Activate time schedule
Write this register to (re-)activate or deactivate the
time schedule
0 = Deactivates the time schedule
1 = Activate the time schedule (this also ends tempo-
rary override)
2 = Set time schedule in edit mode
49061
RW* UI schedule type
1 = 24h (Every day the same)
2 = 5-2 (Mo-Fr, Sa-Su)
3 = 7 day
49062
RW* Switch Points Per Day
Value between 1 (default) till 6
38 INBEDRIJFSTELLING EN INREGELING
Naam / functie
Verklaring