Parameters Modbus:
Iedere ventilatie-unit heeft standaard modbus adres 1. Om dit adres te
wijzigen dient u de Vasco Ventilatie Service Tool te gebruiken.
34 INBEDRIJFSTELLING EN INREGELING
40101
R-RF Communication status
0 = No Error
1 = Error (no communication for at least 30 minutes)
40102
R-Battery Status
FFFFh (no battery)
40103
R-Fault status
0 = Fan ok 1 = Fan failure
41000
R-Actual Ventilation speed
0 = OFF
1 = Speed 1, low
2 = Speed 2, medium
3 = Speed 3, high
11 = Speed 1 temporary override, timer
12 = Speed 2 temporary override, timer
13 = Speed 3 temporary override, timer
21 = Absolute minimum speed, away
23 = Absolute maximum speed, boost
24 = Auto mode
41001
R-Actual Exhaust Fan speed
0 = Off
200 = Highest speed
FFh = Not available
41002
R-Actual Inlet Fan speed
0 = Off
200 = Highest speed
FFh = Not available
41003
R-Error Code
0 No fault
1 Nonspecific fault
2 Emergency stop
3 Fan 1 supply error
4 X22 sensor error
5 X23 sensor error
6 X21 sensor error
7 X20 sensor error
8 Fan 2 error
254 Binding mode active
255 Device identification active
41004
R-Remaining Time
Temporary override
Note: this value is only valid when the actual Ventila-
tion speed equals 11, 12, or 13
41005-41006
R-Indoor Temperature
Value equals NAN when there is no known outdoor
temperature available. A value below -273°C indicates
there is problem with the sensor.
41007-41008
R-Outdoor Temperature
Value equals NAN when there is no known outdoor
temperature available. A value below -273°C indicates
there is problem with the sensor.
Naam / functie
Verklaring
Instelling
Waarde
Baudrate
9600
Data bits
8
Stop bits
1
Parity
Even