41009-41010
R-Exhaust Temperature
Value equals NAN when there is no known outdoor
temperature available. A value below -273°C indicates
there is problem with the sensor.
41011-41012
R-Supply Temperature
Value equals NAN when there is no known outdoor
temperature available A value below -273°C indicates
there is problem with the sensor.
41013
R-Preheater
0% = Preheater off
100% = Pre heater maximum
EFh = Not available
41014
R-Filter Dirty
0 = Filter OK
1 = Filter dirty
41015
R-Defrost
0 = Defrost inactive
1 = Defrost active
41016
R-Bypass position
0% = closed
100% = Open
EFh = Not available
F0h = Actuator Open Circuit
F1h = Actuator Short Circuit
F2h = Not available Error
FDh = Damper/Valve Jam
FEh = Actuator Jam
FFh = Non-specified fault
Note: Values above 120% indicates an error. Value =
EFh Not available in VMD-02RPS54
41017
R-Indoor Humidity
EFh = not available
F0h = shorted sensor
F1h = open sensor
F2h = not available error
F3h = out of range high
F4h = out of range low
F5h = not reliable
F6h-FEh = reserved error
FFh = non-specified error
41019-41020
R-Inlet Flow Level
Special values:
7FFFh: Not Available
8000h-85FFh: sensor error
Note: Value = 7FFFh Not available in VMD-02RPS54
41021-41022
R-Exhaust Flow Level
Special values: 7FFFh: Not Available 8000h-85FFh:
sensor error Note: Value = 7FFFh Not available in
VMD-02RPS54
41023
R-Air Quality
0% = Poor
100% = Excellent
EFh = Not available
Note: Value = EFh Not available in VMD-02RPS54
41024
R-Air Quality Basis
bit 0: VOC based
bit 1: CO
2
based
bit 2: Rh based
Note: Value = 0 Not available in VMD-02RPS54
41025
R-CO
2
level
Special values:
7FFFh: Not Available
8000h-FFFFh: sensor error