H High Performance Universal Inverter User Manual
62 Chapter
6
Parameter
Description
all the function codes.
7: Realize the circular switching of the display modes of last changed 10 function codes and all the
function codes.
8: Realize the circular switching of different function code display modes (basic menu mode
→
fast menu
mode
→
menu mode of non
−
factory setting function code
→
Menu mode of last changed 0 function codes,
refer to description of P0.02 for the menu modes.
Up to 4 parameters can be set and display at running status, and viewed circularly by pressing >>key.
Display of operation panel
0: Reference frequency (Hz) ;
1: Bus voltage (V) ;
2: AI1 (V) ;
3: AI2 (V) ;
4: Reserved;
5: Reserved;
6: External counts
7: Motor rotation speed (rpm);
8: Close loop reference (%);
9: Close loop feedback (%);
A: Reserved;
B: Operating frequency (Hz);
C: Output current (A);
D: Output torque (%);
Unit place:
E: Output power (kW);
F: Output voltage (V)
Tens place
Same as above
Hundreds place
Same as above
Thousands place
Same as above
If the parameter to be displayed has proportion relation with a physical value in the operation display
parameter defined by P2.02, P2.04 can be used to designate the physical value as the display
benchmark, and P2.05 can be used to set the coefficient of the display benchmark.
When the proportion display parameter is set (i.e. P2.05
≠
0), the physical value will be automatically
added into the operation display parameter group and can be viewed by pressing >>key. At this time,
there are 5 display parameters. The LEDs for the newly added parameter are LED A and LED V, both of
which shall be on.
Up to 4 parameters can be set and display in stopping status, and viewed circularly by pressing >>key.
P2.03
Displayed parameter selection in stopping status
0~FFFF(3210)
Display parameter selection at running status
P2.02
0~FFFF(1CB0)
P2.04
Running proportion display benchmark
0~F(0)
P2.05
Running proportion display coefficient
0.0~655.35% (0.00%)