104 Chapter
6
Parameter
Description
Through P1.05 choose the actual pressure feedback channel.
When P1.05=1, the actual pressure feedback determinate by analog input terminal AI1, the pressure
target value 0 to 10V corresponding to 0 to H0.01 setting value.
When P1.05=2, the actual pressure feedback determinate by analog input terminal AI2, the pressure
target value 0 to 20mA corresponding to 0 to H0.01 setting value.
Note:
◆
The input analog through the jumper select 0~10V or 0~20mA
◆
The value of P1.05 and H0.04 can not be set the same value
The two function code may limit the pressure to set high and low limits. When the setting value excess the
value of H0.02 to H0.03, actual pressure target value take the the limit value of H0.02 or H0.03.
This function realized energy saving control for fan or pump.
When the actual running frequency lower than the sleeping frequency reference (H0.06), and continued to
maintain the delay time defined by H0.07, the inverter slow down to 0 frequency, this time motor stops.
When the actual pressure feedback lower than wake up pressure percentage reference(H0.08), and
continued to maintain the delay time defined by H0.09, the inverter re
−
enter the PID regulator, the motor
start running.
Note: In the sleeping status, the operation panel of inverter display “
−
SL
−
”
The function realized auto switch acceleration time and deceleration time during acceleration and
deceleration.
When the frequency reference lower than H0.11, the inverter will automatically switch to acceleration and
deceleration time define by H0.12.
For example, if setting frequency is 0 to 10Hz, the acceleration and deceleration time is 20.0s; if setting
frequency is 10.00Hz to maximum frequency, acceleration and deceleration time is 6.0s, the below
function code should be set: H0.11=10.00Hz,H0.12=1 (using acceleration and deceleration time 1),
P0.08=6.0s,P0.09=6.0s. P4.09=20.0s
,
P4.10=20.0s.
When setting H0.30 to 0, Sleeping and wake up mode acoording the function code of H0.00.
When setting H0.30 to 1, Sleeping and wake up mode acoording the function code of H0.31 to H0.34.
H0.02
High limit of pressure reference
0.00
~
655.35Mpa
(
1.00Mpa
)
H0.03
Low limit of pressure reference
0.00
~
655.35Mpa
(
0.00Mpa
)
H0.06
Sleeping frequency reference
0.00
~
300.00 Hz
(
30.00Hz
)
H0.07
Enter sleeping delay time
0.0
~
3600.0 s
(
60.0s
)
H0.08
Wake up pressure percentage reference
0.0
~
200.0 %
(
50%
)
H0.09
Wake up delay time
0.0
~
3600.0 s
(
30.0s
)
H0.11
The frequency of auto switch acceleration time and
deceleration time
0.00
~
300.00 Hz
(
0.00Hz
)
H0.12
Acceleration time and deceleration time auto switch
selection
0
~
3
(
1
)
H0.30
Sleeping and wake up mode selection
0
~
1
(
0
)