Chapter 6 Parameter Description
73
Figure 6
−
13 X1/X2 terminal delay
Note: The signal can be identified only when the X1/X2 signal pulse width larger than X1/X2 terminal
delay time. See Figure 6
−
13, t
w1
can be identified and t
w2
will be ignored.
P5.11 is used to set the mode of controlling the startup and stop of the inverter with FWD and REV
terminals when the running command is issued via terminal.
0: Two line 1;
COM
FWD
REV
K1
K2
变
频
器
Inverter
COM
FWD
REV
K1
K2
变
频
器
Inverter
Figure 6
−
14 Two
−
line running mode 1
1: Two line 2;
Inverter
Inverter
Figure 6
−
15 Two
−
line running mode 2
FWD REV
Start
−
up and
stop
command
0 0 Stop
0 1
Run
reverse
1 0
Run
forward
1 1 Stop
FWD REV
Start
−
up and
Stop
0 0 Stop
0 1 Stop
1 0
Run
forward
1 1
Run
reverse
P5.11
Startup/stop mode Selection
0 ~ 3(0)