3.4 Vacon 100 Wizard.
The Startup Wizard allows you to quickly change the basic settings to values that best suit
your application.
The following keys are used in the wizard:
Arrows left and right; these change digits and decimals.
Arrows up and down; scroll through the various options, and change
values.
This confirms the selection.
Pressing this key returns you to the previous question in the wizard. If this key is
pressed during the first question, the wizard closes.
3.5 Startup Wizard.
When the frequency converter is started for the first time, it automatically starts the Startup
Wizard, which can also be started with parameter (P1.1.1)
Setting
Value
1 Language selection
2 Daylight saving time
(only with a battery power
supply)
Russia
US
EU
OFF
3 Time setting
hh:mm:ss
4 Year setting
- - - -
5 Date setting
dd:mm
6 Use Startup Wizard?
Yes
No
(exit wizard)
7 Application
Standard
HVAC
PID control
Multi-pump
(single drive)
Multi-pump
(multi-drive)
8
Motor type
PM motor
(permanent magnet)
Induction motor
Reluctance motor
9 Rated motor voltage
(see motor nameplate)
Varies
10 Rated motor frequency
(see motor nameplate)
8 to 320 Hz.
11 Rated motor speed
(see motor nameplate)
24 to 19,200 rpm
12 Rated motor current
(see motor nameplate)
Varies
13 Motor Cos Phi
(see motor nameplate)
0.30 to 1.00
14 Minimum frequency
0 to
max. frequency
Hz.
15 Maximum frequency
min frequency
to 320 Hz.
16 Acceleration time 1
0.1 to 3,000 sec
17 deceleration time 1
0.1 to 3,000 sec
18 Application Wizard
Yes*
No
(exit wizard)
*) If yes is selected, the key parameters are gone through for each application.
BACK
RESET
OK