Vacon 100 Flow
page
36
8.2 Multi-pump Multi-drive application (Wizard)
Please note! The factory setting must always be used as a starting point when using the
application examples in this book. (P6.5.1)
With the Multi-Pump (Multi-Drive) application, the following parameters appear:
Step
Parameter
Number
Description
1
Motor type
P3.1.2.2
Permanent magnet or induction motor
2
Rated voltage
P3.1.1.1
Varies
3
Rated motor frequency
P3.1.1.2
8 to 320 Hz.
4
Rated motor speed
P3.1.1.3
24 to 19,200 rpm
5
Rated motor current
P3.1.1.4
Varies
6
Cos phi of the motor
P3.1.1.5
0.3 to 1
7
Minimum frequency
P3.3.1.1
0 Hz. … P3.3.1.2
8
Maximum frequency
P3.3.1.2
P3.3.1.1 … 320 Hz.
9
Acceleration time
P3.4.1.2
0.1 to 300 s
10
Deceleration
P3.4.1.3
0.1 to 300 s
11
Control location
I/O - terminals
Fieldbus
Control Panel
12
Selection of process unit
P3.13.1.4
Various options
13
Minimum process unit
P3.13.1.5
Minimum value of sensor, e.g. (0 to 10 bar) = 0 bar
14
Maximum process unit
P3.13.1.6
Maximum value of sensor, e.g. 10 bar
15
Decimal process unit
P3.13.1.7
Decimal places (0 to 0.0000)
16
Feedback 1 source selection
P3.13.3.3
Position sensor, e.g. (AI 2)
17
Signal range analogue inputs
0 to 10 V/0 to 20 mA
2 to 10 V/4 to 20 mA
18
Inversion error
P3.13.1.8
Normal/inverted
19
Reference point source selection
P3.13.2.6
Reference location PID (Control panel reference point 1)
20
Control panel reference point 1
P3.13.2.1
Fill in operating point
21
Sleep function?
Yes
Step 20
No
Step 23
22
Sleep frequency
P3.13.5.1
0 to 320 Hz.
23
Sleep delay 1
P3.13.5.2
0 to 3,000 s
24
Wake-up level
P3.13.5.3
Regulator starting point
25
Multi-pump mode
P3.15.1
Multi-follower / Multi-master
26
Pump ID number
P3.15.3
1 to 8
27
Start and feedback
P3.15.4
Signals connected/Only start signal/Disconnected
28
Number of pumps
P3.15.2
1 to 8
29
Pump block
P3.15.5
Unused/Unblocked
30
Autochange
P3.15.6
Blocked
Step 34
Enabled (interval)
Step 31, 34
Enabled (weekdays) Step 32
31
Autochange interval
P3.15.8
0 to 3,000 h
32
Autochange days
P3.15.9
Sunday to Saturday
33
Autochange time
P3.15.10
00:00:00 to 23:59:59
34
Range
P3.15.13
0 to 100%
35
Range delay
P3.15.14
0 to 3600 s