6.2.2.2 Terminals
According to the settings of PID control 6.2.2.1
Basic I/O board
terminal
signal
description (PID settings)
1
+10 V
ref
Reference output
Power supply for potentiometer, etc.
2
AI 1+
Analogue input, 0 to 10 V DC or
0/4 to 20 mA
Voltage input frequency reference
3
AI 1-
Analogue input reference
potential
Reference potential inputs and outputs
4
AI 2+
Analogue input, 0 to 10 V DC or
0/4 to 20 mA
Programmable current input
5
AI 2-
Analogue input reference
potential
6
+ 24 V Output voltage control
Power supply for contacts, etc. max 0.1 A
7
GND
I/O reference potential
Reference potential inputs and outputs
8
DI 1
Digital input 1
Start PID (programmable contact)
9
DI 2
Digital input 2
External error if contact is broken
(programmable contact)
10
DI 3
Digital input 3
reset failure (programmable contact)
11
CM
Additional reference potential
for DI 1 to DI 6
Is connected to GND (earth). Can also be
insulated from GND by jumpers
12
+ 24 V Output voltage control
Power supply for contacts, etc. max 0.1 A
13
GND
I/O reference potential
Reference potential inputs and outputs
14
DI 4
Digital input 4
Fixed frequency selection 0. (Binary)
(programmable contact)
15
DI 5
Digital input 5
PID reference 2 (programmable contact)
16
DI 6
Digital input 6
Switching between control signal source
(programmable contact)
17
CM
Additional reference potential
for DI 1 to DI 6
Is connected to GND (earth). Can also be
insulated from GND by jumpers
18
AO 1+
Analogue output
Programmable
range 0 to 20 mA / R max 500.
19 AO-/GND
30 +24 V in 24 V input voltage
A
RS-485
B
RS-485
Relay board 1
21 RO1 nc
Relay output 1 Programmable (run)
22 RO1 com
23 RO1 no
24 RO2 nc
Relay output 2 Programmable (fault)
25 RO2 com
26 RO2 no
32 RO3 com
Relay output 3 Programmable (ready)
33 RO3 no