2 Wiring and display
2.1 Cable diameter and fuses
Frame
Type
I
L
[A]
Fuse
(gG/g
L) [A]
Mains and motor
cable
Cu [mm
2
]
Terminal size
Mains
connection
[mm
2
]
Earth
connection
[mm
2
]
MR4
0003 4 - 0004 4
3.4 to 4.8
6
3 x 1.5 + 1.5
1 to 6 solid
1 to 4 flexible
1 to 6
0005 4 -0008 4
5.6 to 8.0
10
3 x 1.5 + 1.5
1 to 6 solid
1 to 4 flexible
1 to 6
0009 4 -0012 4
9.6 to 12.0 16
3 x 1.5 + 1.5
1 to 6 solid
1 to 4 flexible
1 to 6
MR5
0016 4
16.0
20
3 x 6 + 6
1 to 10 Cu
1 to 10
0023 4
23.0
25
3 x 6 + 6
1 to 10 Cu
1 to 10
0031 4
31.0
32
3 x 10 + 10
1 to 10 Cu
1 to 10
MR6
0038 4
38.0
40
3 x 10 + 10
2.5 to 50 Cu/Al 2.5 to 35
0046 4
46.0
50
3 x 16 + 16 (Cu)
3 x 25 + 16 (Al)
2.5 to 50 Cu/Al 2.5 to 35
0061 4
61.0
63
3 x 25 + 16 (Cu)
3 x 35 + 10 (Al)
2.5 to 50 Cu/Al 2.5 to 35
MR7
0072 4
72.0
80
3 x 35 + 16 (Cu)
3 x 50 + 16 (Al)
6 to 70 Cu/Al
6 to 70
0087 4
87.0
100
3 x 35 + 16 (Cu)
3 x 70 + 21 (Al)
6 to 70 Cu/Al
6 to 70
0105 4
105.0
125
3 x 50 + 25 (Cu)
3 x 70 + 21 (Al)
6 to 70 Cu/Al
6 to 70
MR8
0140 4
140.0
160
3 x 70 + 35 (Cu)
3 x 95 + 29 (Al)
Bolt size M8
Bolt size M8
0170 4
170.0
200
3 x 95 + 50 (Cu)
3 x 150 + 41 (Al)
Bolt size M8
Bolt size M8
0205 4
205.0
250
3 x 120 + 70 (Cu)
3 x 185 + 57 (Al)
Bolt size M8
Bolt size M8
MR9
0261 4
261.0
315
3 x 185 + 95 (Cu)
2 x 3 x 120 + 41 (Al) Bolt size M8
Bolt size M8
0310 4
310.0
350
2 x 3 x 95 +50 (Cu)
2 x 3 x 120 + 41 (Al) Bolt size M8
Bolt size M8
2.2 Shielded cables
The cables of the control signals and of the motor must be shielded in order to meet radio
interference rules, in accordance with IEC 60364-5-52 and EMC specifications.
The shielding of the motor and control cables must be connected to the earth terminal in
the frequency converter and in the motor and sensors, PLC etc.
If unshielded cables are used, signal interference can occur in the control inputs. Such
interference will not normally damage the frequency converter, but will interfere with
regulation.
Max. length of motor
cable
MR4
MR5 and MR6
MR7, MR8 and MR9
100 m
150 m
200 m
Be careful! Reinforcement designed as mechanical protection (e.g. earth cable) is not
suitable for an EMC-correct installation.
Our preference is to use twisted cable for signal cables.