Vacon 100 Flow
page
16
Default
Code
Parameter
slot position Description
P3.5.1.39
Close fire mode activation
0
1
Open:
No action
Closed: Fire mode active (M3.17)
P3.5.1.40
Fire mode reverse
0
1
Open:
Forward
Closed: Reverse This function is only active in fire mode
P3.5.1.41
Auto cleaning active
0
1
Closed: Auto cleaning active (on opening, the function stops)
Please note! Regulator starts when activating this function
P3.5.1.42
Pump 1 block
0
1
Open:
Inactive
Closed: Active
P3.5.1.43
Pump 2 block
0
1
Open:
Inactive
Closed: Active
P3.5.1.44
Pump 3 block
0
1
Open:
Inactive
Closed: Active
P3.5.1.45
Pump 4 block
0
1
Open:
Inactive
Closed: Active
P3.5.1.46
Pump 5 block
0
1
Open:
Inactive
Closed: Active
P3.5.1.47
Pump 6 block
0
1
Open:
Inactive
Closed: Active
P3.5.1.48
Pump 7 block
0
1
Open:
Inactive
Closed: Active
P3.5.1.49
Pump 8 block
0
1
Open:
Inactive
Closed: Active
P3.5.1.52
Energy counter reset
0
1
Closed: Energy trip counter reset
P3.5.1.53
Parameter set 1/2 selection
0
1
Open:
Parameter setting 1 is selected
Closed: Parameter setting 2 is selected
P3.5.1.54
Multi setpoint select 0
0
1
Binary selection for multi setpoint
P3.5.1.55
Multi setpoint select 1
0
1
Binary selection for multi setpoint
P3.5.1.56
Multi setpoint select 2
0
1
Binary selection for multi setpoint
P3.5.1.57
Multi setpoint select 3
0
1
Binary selection for multi setpoint
P3.5.1.58
Flow switch
0
2
Select digital input flow switch
P3.5.1.59
AHF over temperature
0
1
Activate AHF over temperature
The default values listed above are applicable when using the default application. These
values may change if other applications are used