Vacon 100 Flow
page
15
3.8.1 Functions for DI
Default
Code
Parameter
slot position Description
P3.5.1.1
Control signal 1 A
A
1
If I/O A is the operating location (forward)
P3.5.1.2
Control signal 2 A
A
2
If I/O A is the operating location (reverse)
P3.5.1.3
Control signal 3 A
0
1
If I/O A is the operating location
P3.5.1.4
Control signal 1 B
0
1
If I/O B is the operating location
P3.5.1.5
Control signal 2 B
0
1
If I/O B is the operating location
P3.5.1.6
Control signal 3 B
0
1
If I/O B is the operating location
P3.5.1.7
Force to I/O B control signal
0
1
Select control signal B
P3.5.1.8
Force to I/O B reference
0
1
Use reference value control signal B (M3.3.1.6)
P3.5.1.9
Force to fieldbus control
0
1
Force operation to fieldbus
P3.5.1.10
Force to display operation
0
1
Force operation to control panel
P3.5.1.11
Close external error
A
3
Open: OK
Closed: External error
P3.5.1.12
Open external error
0
2
Open:
External error
Closed: Ok
P3.5.1.13
Close error reset
A
6
Closed: Reset all active errors
P3.5.1.14
Open error reset
0
1
Open:
Reset all active errors
P3.5.1.15
Release
0
2
Closed: regulator is ready
P3.5.1.16
Start block 1
0
2
Open:
Regulator ready, starting blocked
Closed: Regulator can be started
P3.5.1.17
Start block 2
0
2
Open:
Regulator ready, starting blocked
Closed: Regulator can be started
P3.5.1.18
Preheating ON
0
1
Open:
No action
Closed: Preheat activated if (P3.18.1 is set to 2)
P3.5.1.19
Ramp 2 selection
0
1
Switching between ramp 1 and 2
P3.5.1.20
Acc/dec prohibited
0
1
Open:
Acceleration and deceleration permitted
Closed: Acceleration and deceleration not permitted
P3.5.1.21
Fixed frequency selection 0
A
4
Binary selection for fixed frequency
P3.5.1.22
Fixed frequency selection 1
A
5
Binary selection for fixed frequency
P3.5.1.23
Fixed frequency selection 2
0
1
Binary selection for fixed frequency
P3.5.1.24
Increase motor pot
0
1
Motor pot reference goes up
P3.5.1.25
Decrease motor pot
0
1
Motor pot reference goes down
P3.5.1.26
Quick stop activation
0
2
Open:
Activated according to (P3.9.5)
P3.5.1.27
Timer 1
0
1
Start Timer 1 programmed with parameters (P3.12.6)
P3.5.1.28
Timer 2
0
1
Start Timer 2 programmed with parameters (P3.12.7)
P3.5.1.29
Timer 3
0
1
Start Timer 3 programmed with parameters (P3.12.8)
P3.5.1.30
PID 1 reference increase
0
1
Open:
No amplification
Closed: Amplification
P3.5.1.31
PID 1 SP selection
0
1
Open:
Reference value 1
Closed: Reference value 2
P3.5.1.32
External PID - start signal
0
2
Open:
External PID stopped
Closed: External PID controls (P3.14)
P3.5.1.33
External PID SP selection
0
1
Open:
Reference value 1
Closed: Reference value 2
P3.5.1.34
Reset maintenance counter 1
0
1
Closed: Reset maintenance counter
P3.5.1.36
Activate flushing reference
0
1
Closed: Flushing function active (P3.3.6.2)
Please note! Regulator starts when activating this function
P3.5.1.38
Open fire mode activation
0
2
Open:
Fire mode active (M3.17)
Closed: No action