Table 13 R Command
Syntax
Description
r
<cr>
Start the continuous outputting of measurement
values as an ASCII text string to the serial line.
Example (measurement message in default format):
r
T= 22.8 'C RH= 39.5 %RH Td= 8.3 'C Tw= 14.5 'C h= 40.4 kJ/kg
T= 22.8 'C RH= 39.5 %RH Td= 8.3 'C Tw= 14.5 'C h= 40.4 kJ/kg
...
Table 14 S Command
Syntax
Description
s
<cr>
Stop the continuous outputting of measurement
values.
Example:
...
T= 22.8 'C RH= 39.5 %RH Td= 8.3 'C Tw= 14.5 'C h= 40.4 kJ/kg
T= 22.8 'C RH= 39.5 %RH Td= 8.3 'C Tw= 14.5 'C h= 40.4 kJ/kg
s
Since the interface is half-duplex, you must enter the
s
command when the
device is not outputting.
Table 15 Intv Command
Syntax
Description
intv
<cr>
Show the output interval of the automatically
repeating measurement messages (r command
and run mode).
intv [iii u]
<cr>
Set the output interval.
iii = interval, range 0 ... 255.
u = unit for interval setting:
• s = seconds
• min = minutes
• h = hours
If you set the interval to 0, the output messages
are output as quickly as they are generated,
without additional delay.