Despite the specification, some Modbus masters may expect "big-endian" word order (most
significant word first). In such case, you must select "word-swapped" floating point format in
your Modbus master for the Modbus registers of the device.
Reading the measurement data registers with incorrect floating point format setting may
occasionally result in correct-looking values. It is highly recommended to first try reading the
register number 7938 (floating point test) to see that you have configured the floating point
format correctly on your Modbus host system.
A complete 32-bit floating point value should be read and written in a single
Modbus transaction.
A.4 Modbus Registers
Registers are numbered in decimal, starting from one. Register
addresses in actual Modbus messages (Modbus Protocol Data Unit (PDU)) start
from zero.
Please check the reference documentation of your Modbus host (PLC) for the
notation of Modbus register addresses.
CAUTION!
A.4.1 Measurement Data Registers
Table 51 Modbus Measurement Data Registers (Read-Only)
Register
Number
(Decimal)
Address
(Hexadecimal)
Register Description
Data Format
Unit
1
0000
hex
Relative humidity
32-bit float
%RH
3
0002
hex
Temperature
32-bit float
°C
9
0008
hex
Dew/frost point
temperature
32-bit float
°C
19
0012
hex
Wet bulb temperature
32-bit float
°C
27
001A
hex
Enthalpy
32-bit float
kJ/kg
Accessing unavailable (temporarily missing) measurement data does not generate an
exception. “Unavailable” value (a quiet NaN) is returned instead.
Appendix A – Modbus Reference
79
Summary of Contents for hmdw110 series
Page 1: ...M211726EN D User Guide Vaisala Humidity and Temperature Transmitter Series HMDW110 ...
Page 5: ...Recycling 87 Table of Contents 3 ...
Page 87: ...Appendix A Modbus Reference 85 ...
Page 88: ...HMDW110 User Guide M211726EN D 86 ...
Page 90: ...HMDW110 User Guide M211726EN D 88 ...
Page 91: ......
Page 92: ...www vaisala com ...