Syntax
Description
Example (enable 10 % overrange for analog outputs):
aover on
AOVER : ON
Table 29 Asel Command
Syntax
Description
asel ?
<cr>
Show currently set analog output parameters
and scaling.
asel
<cr>
Show currently set analog output parameters
and scaling, prompt to enter new scaling values.
asel [ch1 ch2]
<cr>
Set new output parameters for both channels,
prompt to enter new scaling values. Selectable
parameters for ch1 and ch2 are:
t = temperature
rh = relative humidity
td = dew point
h = enthalpy
tw = wet bulb temperature
asel
[ch1 ch2 [ch1lo ch1hi ch2lo ch2hi]
]
<cr>
Set analog output parameters and scaling for
both channels without prompting.
ch1 = Output parameter for channel 1.
Parameters as above.
ch2 = Output parameter for channel 2.
Parameters as above.
ch1lo = Low limit for channel 1 scaling.
ch1hi = High limit for channel 1 scaling.
ch2lo = Low limit for channel 2 scaling.
ch2hi =High limit for channel 2 scaling.
Example (show current analog output parameters and scaling):
asel ?
Ch1 RH lo : 0.00 %RH
Ch1 RH hi : 100.00 %RH
Ch2 T lo : -40.00 'C
Ch2 T hi : 60.00 'C
Chapter 6 – Using Service Port With Terminal Application