A.4.3 Configuration Registers
Table 54 Modbus Configuration Data Registers (Writable)
Register
Number
(Decimal)
Address
(Hexadecimal)
Register Description
Data
Format
Unit / Valid Range
Filtering
785
0310
hex
Filtering factor
32-bit float
0.001 (maximum
filtering) ... 1.000 (no
filtering)
Communication
1537
0600
hex
Modbus address
16-bit
integer
1 ... 247
1538
0601
hex
Bit rate (b/s)
16-bit
integer
5 = 9600
6 = 19200
7 = 38400
8 = 57600
1539
0602
hex
Parity, data, stop bits
16-bit
integer
0 = N81
1 = N82
2 = E81
3 = E82
4 = O81
5 = O82
1540
0603
hex
Response delay
16-bit
integer
0 ... 1020 ms
1541
0604
hex
Protocol
16-bit
integer
6 = Modbus RTU
Functions
1542
0605
hex
Restart device
16-bit
integer
Write 1 to restart device
1)
Changed setting will be activated on device restart.
Appendix A – Modbus Reference
81