FAULT TRACKING
vacon • 27
24-hour s358 (0)40 837 1150 • Email: [email protected]
APPENDIX 1
Vacon DeviceNet Interface Errors
The OPTC7 DeviceNet interface records the following events in the Event List FIFO:
VACON Event Name
Event Code
Event Description
No event
0x00
Default value in EventList
entries.
Drive Communication Error
0x01
Inverter interface communication
error with the drive.
I/O Connection Timeout – Fault_Stop
0x02
Control Supervisor transitions to Fault_Stop.
I/O Connection Timeout – No Action
0x03
Control Supervisor remains in Enabled State.
Hold last speed
I/O Connection Timeout – Preset
Direction and Speed
0x04
Control Supervisor remains in Enabled State.
Run at preset direction and speed.
Explicit Connection Timeout – Fault_Stop
0x05
Control Supervisor transitions to Fault_Stop.
Explicit Connection Timeout – No Action
0x06
Control Supervisor remains in Enabled State.
Hold last speed
Explicit Connection Timeout – Preset
Direction and Speed
0x07
Control Supervisor remains in Enabled State.
Run at preset direction and speed.
Low DeviceNet Voltage
0x08
Connection timeout may occur next.
Bus Off
0x09
Connection timeout may occur next.
CAN Overrun
0x0C
Connection timeout may occur next.
Configuration Consistency Value (CRC)
mismatch
0x0E
The device’s configuration is incorrect or
incomplete. Major Recoverable Fault. An
Identity Reset type 1 is needed for recovery.
Microprocessor watchdog timeout
0x0F
The device detected a serious problem with
itself. Major Unrecoverable Fault.
Received explicit message is too big
0x10
Message is ignored.
Received IO message is too big
0x11
Message is ignored.
Parameter Range Error
0x12
An out-of-range parameter value exists in
the drive.
I/O Connection Released – Fault_Stop
0x14
Control Supervisor transitions to Fault_Stop.
I/O Connection Released – No Action
0x15
Control Supervisor remains in Enabled State.
Hold last speed
I/O Connection Released – Preset Direction
and Speed
0x16
Control Supervisor remains in Enabled State.
Run at preset direction and speed.
Receive_Idle – Fault_Stop
0x17
Control Supervisor transitions to Fault_Stop.
Receive_Idle – No Action
0x18
Control Supervisor remains in Enabled State.
Hold last speed
Receive_Idle – Preset Direction and Speed
0x19
Control Supervisor remains in Enabled State.
Run at preset direction and speed.
Explicit Connection Released – Fault_Stop
0x1A
Control Supervisor transitions to Fault_Stop.
Explicit Connection Released – No Action
0x1B
Control Supervisor remains in Enabled State.
Hold last speed
Explicit Connection Released – Preset
Direction and Speed
0x1C
Control Supervisor remains in Enabled State.
Run at preset direction and speed.