FAULT TRACKING
vacon • 41
24-hour s358 (0)40 837 1150 • Email: [email protected]
Motor Data Object Class (40) - Class Attributes (1)
#
Attribute Name
Services
Default,
Data
Description
Minimum,
Type
Maximum
3
0x03
Motor Type
Get_Attribute_Single
7
7
7
C6
Type of Motor Represented by This
Instance
0 – Non-standard motor
1 - PM DC Motor
2 - FC DC Motor
3 - PM Synchronous Motor
4 - FC Synchronous Motor
5 - Switched Reluctance Motor
6 - Wound Rotor Induction Motor
7 - Squirrel Cage Induction Motor
8 - Stepper Motor
9 - Sinusoidal PM BL Motor
10 - Trapezoidal PM BL Motor
6 RatedCurrent[100mA
]
Get_Attribute_Single
70 C7
Rated Stator Current
0x06
0
Units: [100mA]
16000
7 RatedVoltage[V]
Get_Attribute_Single
230 C7
Rated Base Voltage
0x07
180
Units: [V]
690
9 RatedFrequency[Hz] Get_Attribute_Single
50 C7
Rated Electrical Frequency
0x09
30
Units: [Hz]
500
12 PoleCount[pair*2]
Get_Attribute_Single
4 C7
Number of poles in the motor
0x0C
2
16
15
0x0F
BaseSpeed[RPM]
Get_Attribute_Single
1440
1
30000
C7
Nominal speed at rated frequency from
nameplate
Units: [RPM]
176
0xB0
User Label
Get_Attribute_Single,
Set_Attribute_Single
N/A
N/A
N/A
DA
User Supplied name for the Instance.
Maximum of 8 characters