FAULT TRACKING
vacon • 49
24-hour s358 (0)40 837 1150 • Email: [email protected]
Monitoring Data Class (170) - Class Attributes (1)
#
Attribute Name
Services
Default,
Data
Description
Minimum,
Type
Maximum
1-99
Get_Attribute_Single
N/A
N/A
N/A
C7
Actual Values. Attributes are defined in
EDS file (Depend on drive application).
0x01-
0x63
101
0x65
E1
Get_Attribute_Single,
Set_Attribute_Single
N/A
0
65535
C7
102
0x66
E2
Get_Attribute_Single,
Set_Attribute_Single
N/A
0
65535
C7
103
0x67
E3
Get_Attribute_Single,
Set_Attribute_Single
N/A
0
65535
C7
104
0x68
E4
Get_Attribute_Single,
Set_Attribute_Single
N/A
0
65535
C7
105
0x69
E5
Get_Attribute_Single,
Set_Attribute_Single
N/A
0
65535
C7
106
0x6A
E6
Get_Attribute_Single,
Set_Attribute_Single
N/A
0
65535
C7
107
0x6B
E7
Get_Attribute_Single,
Set_Attribute_Single
N/A
0
65535
C7
108
0x6C
E8
Get_Attribute_Single,
Set_Attribute_Single
N/A
0
65535
C7
109
0x6D
EC
Get_Attribute_Single,
Set_Attribute_Single
N/A
0
65535
C7
110
0x6E
SafeStateType
Get_Attribute_Single,
Set_Attribute_Single
0
0
2
C7
Selects Safe State response to errors
which specify safe state operation.
Currently only a loss of connection other
than by de-allocation is a safe state error.
Alarm: Review the application for safe
operation before specifying a value for
this attribute.
0 = DriveFault (fault and stop)
1 = No Action (hold last speed)
2 = Preset Speed/Direction
111
0x6F
PresetDir
Get_Attribute_Single,
Set_Attribute_Single
N/A
0
1
C7
Sets safe state direction of rotation if the
Safe State Behavior attribute specifies
"Preset Speed/Direction" .
Alarm: Review the application for safe
operation before specifying a value for
this attribute.
Inverter will require external stop.
0 = Forward
1 = Reverse
Summary of Contents for NX OPTC7
Page 1: ...vacon nx ac drives optc7 devicenet option board user manual ...
Page 51: ......