26 • vacon
FAULT TRACKING
8.
FAULT TRACKING
The table below presents the faults related to the DeviceNet option board. For more information, see
also Vacon NX User's Manual, Chapter 9.
The DeviceNet option board status LEDs have been described in more detail in Chapter 4.2
Fault
code
Fault
Possible cause
Correcting measures
37
Device change
Option board changed.
Reset
38
Device added
Option board added.
Reset
39
Device removed Option board removed.
Reset
40
Device
unknown
Unknown option board.
53
Fieldbus fault
The data connection between the
DeviceNet Master and the DeviceNet
option board is broken
Check the installation.
If installation is correct contact the
nearest Vacon distributor.
54
Slot fault
Defective option board or slot
Check the board and slot.
Contact the nearest Vacon distributor.
Table 8-1. DeviceNet option board faults
You can define with parameters how the frequency converter shall react to certain faults:
Code
Parameter
Min
Max
Unit
Step
Default
ID
Note
P2.7.22 Response to fieldbus
fault
0
3
1
0
733
0=No response
1=Alarm
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
P2.7.23
Response to slot
fault
0
3
1
0
734
0=No response
1=Alarm
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
Table 8-2. Frequency converter responses to faults