6.7
Protections
6.7.1
General
Code
Parameter
Min
Max
Unit
Default
ID
Description
2.7.1.1
0
3
2
732
0=No response
1=Warning
2=Fault
3=Fault, DC OFF
2.7.1.2
0
3
2
1505
0=No response
1=Warning
2=Fault
3=Fault, DC OFF
2.7.1.3
External Fault
Response
0
3
2
701
0=No response
1=Warning
2=Fault
3=Fault, DC OFF
2.7.1.4
MCB At Fault
0
1
0
1699
2.7.1.5
Charge Max Time
0,00
60,00
s
10,00
1522
Charging time limit when
drive charging options are
used.
Table 5-9. General Protections parameters G2.7.1
6.7.2
Temperature sensor protections
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.7.2.1
0
5
0
739
0=Not used (ID Write)
1 = Sensor 1 in use
2 = Sensor 1 & 2 in use
3 = Sensor 1 & 2 & 3 in use
4 = Sensor 2 & 3 in use
5 = Sensor 3 in use
P2.7.2.2
0
3
2
740
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P2.7.2.3
30,0
200,0
Cº
120,0
741
P2.7.2.4
30,0
200,0
Cº
130,0
742
P2.7.2.5
0
5
0
743
0=Not used (ID Write)
1 = Sensor 1 in use
2 = Sensor 1 & 2 in use
3 = Sensor 1 & 2 & 3 in use
4 = Sensor 2 & 3 in use
5 = Sensor 3 in use
P2.7.2.6
0
3
2
766
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P2.7.2.7
30,0
200,0
Cº
120,0
745
P2.7.2.8
30,0
200,0
Cº
130,0
746
P2.7.2.9.1
Channel 1B Warn
-30,0
200,0
Cº
0,0
764
P2.7.2.9.2
Channel 1B Fault
-30,0
200,0
Cº
0,0
765
P2.7.2.9.3
Channel 1C Warn
-30,0
200,0
Cº
0,0
768
P2.7.2.9.4
Channel 1C Fault
-30,0
200,0
Cº
0,0
769
P2.7.2.9.5
Channel 2B Warn
-30,0
200,0
Cº
0,0
770
P2.7.2.9.6
Channel 2B Fault
-30,0
200,0
Cº
0,0
771
P2.7.2.9.7
Channel 2C Warn
-30,0
200,0
Cº
0,0
772
P2.7.2.9.8
Channel 2C Fault
-30,0
200,0
Cº
0,0
773