26
• Vacon
arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5.2.3
Line monitoring OPT-D7
V1.3.1
Line Voltage
V
ID1650
The measured line voltage rms value when using the OPT-D7 option board in slot C.
V1.3.2
Line Frequency Hz
ID1654
The measured line voltage frequency when using the OPT-D7 option board in slot C.
V1.3.3
Synch Error D7
ID1659
An error on voltage angles between the drive and the measurement taken by OPT-D7.
-3072...+3071 = -180...180 degrees.
If the value is not near to zero when running in AFE mode, the phase order may be wrong
even if the OPT-D7 frequency is correct (Error about 2047 = 120 degree). If measurement
is after Dyn11 transformer error is usually about 512 (30,0 Degree).
V1.3.4
Line Voltage THD
ID1670
V1.3.5
LineVoltageHFrms
ID1671
5.2.4
Master/Follower
Here are gathered relevant signals in Master follower system.
V1.4.1
SB SystemStatus
ID 1601
System Bus Status Word ID1601
FALSE
TRUE
b0
Not used
b1
Drive 1 Ready
b2
Drive 1 Running
b3
Drive 1 Fault
b4
Not used
b5
Drive 2 Ready
b6
Drive 2 Running
b7
Drive 2 Fault
b8
Not used
b9
Drive 3 Ready
b10
Drive 3 Running
b11
Drive 3 Fault
b12
Not used
b13
Drive 4 Ready
b14
Drive 4 Running
b15
Drive 4 Fault
V1.4. 2
Master CW
ID93
Master Drive Control Word. Master Sending, Follower receiving.