Arfiff05 Standard AFE-II
vacon •
59
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
This parameter sets the time constant of the controller for the active current of the
regenerative unit (15 equals 1.5ms).
P2.6.7.8
Synch. Kp Start
ID1300
P2.6.7.9
Voltage Control Kp
ID1451
This parameter sets the gain for the DC link PI voltage controller.
P2.6.7.10 Voltage Control Ti
ID1452
This parameter sets the time constant in ms of the DC link PI controller.
P2.6.7.11 Switching frequency
ID601
The switching frequency of the IGBT bridge in kHz. Changing the default value may
impact on the LCL filter operation.