52
• Vacon
arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
P2.4.2.7
Iout Offset
ID375
Add 100.0 to 100.0% to the analogue output.
100 %
0 %
Scaling
50 %
Function
Signal
0 %
100 %
20 %
50 %
Scaling
200 %
50 %
Analogue
Output
7.4.3
Options outputs
P2.4.3.1
Output Inversion
ID1806
With this parameter it is possible to select which output signals are inverted.
B00 = +1 = Reserved
P2.4.3.1
MCB Close Mode
This parameter defines how the closing of circuit breaker is handled.
0 = DC Voltage
Normal AFE operation type circuit breaker control. The circuit breaker is closed when
DC voltage is at a required level.
1 = DC Voltage or Start Command
The circuit breaker is closed when DC voltage is at the required level, or from a start
command if DC is at a required level. This can be used when the breaker is opened,
for example, by a stop command but DC remains high. It is useful when used in a
battery system.
2 = Start Command
The circuit breaker is closed from a start command if DC is at a required level.