• Vacon
arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
P2.7.2.6
Board 2 Temperature response
ID766
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to Stop Function
3 = Fault, stop mode after fault always by coasting
P2.7.2.7
Board 2 warning limit ID745
Set here the limit at which the second temperature sensor board warning will be
activated. When individual warning and fault limits are activated this is second board first
channel (2A).
P2.7.2.8
Board2 fault limit
ID746
Set here the limit at which the second temperature sensor board fault (F61) will be
activated. When individual warning and fault limits are activated this is second board first
channel (2A).
.7.7.2.1
Individual channel monitoring
Individual channel monitoring is activated by setting one of the warning limits (per board) different
than zero. Common limits in above parameters will be channel A warning and fault limits. Channel B
and C limits are set with below parameters.
P2.7.2.9.1
Channel 1B Warn
ID764
P2.7.2.9.2
Channel 1B Fault
ID765
First board second (1B) channel warning and fault limits.
P2.7.2.9.3
Channel 1C Warn
ID768
P2.7.2.9.4
Channel 1C Fault
ID769
First board third (1C) channel warning and fault limits.
P2.7.2.9.5
Channel 2B Warn
ID770
P2.7.2.9.6
Channel 2B Fault
ID771
Second board second (2B) channel warning and fault limits.
P2.7.2.9.7
Channel 2C Warn
ID772
P2.7.2.9.8
Channel 2C Fault
ID773
Second board third (2C) channel warning and fault limits.
7.7.3
Fieldbus
2.7.3.1
Fieldbus Fault Slot D Response
ID733
Set the response for a fieldbus fault if the active control place is fieldbus. For more
information, see the relevant Fieldbus Board Manual.
0 = No response
1 = Warning