48
• Vacon
arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7.4
Output signals
7.4.1
Digital outputs
P2.4.1.1
MCB Close Control
ID1218
MCB Close
AFE MCB control, fixed to the relay output B.2.
When P2.4.1.2 is not activated, this output will stay high as long as MCB must be closed.
When the signal goes low, MCB must be open.
P2.4.1.2 MCB 1 Open Control
ID1219
MCB OpenControl
When this output is selected above 0.9, the drive will use pulse control for the MCB
breaker. P2.5.1.1 is used to close the breaker with a 2 s pulse.
The opening command is given by with a 2 s pulse.
P2.4.1.3
Ready
ID432
The AC drive is ready to operate.
P2.4.1.4
Run
ID433
The AC drive operates (the drive is modulating).
P2.4.1.5
Fault
ID434
Drive is in fault state
P2.4.1.6
Fault, Inverted
ID435
No active faults.
P2.4.1.7
Warning
ID436
Warning is active.
P2.4.1.8
DC Above Limit
ID451
DC Voltage is above P2.5.5.1 DC Supervision limit.
P2.4.1.9
DC Charge
ID1668
This output function is used to charge DC. When run enable is HIGH and there are no
active faults, the rising edge on the start command will start the DC charging and if
charging is successful, the drive will go to Run State. In fieldbus control, charging is
started by FB Control Word B0. If MCB feedback is not received within P:Max Charge
Time, fault F80 is generated.
Summary of Contents for NX ACTIVE FRONT END II
Page 1: ...vacon nx ac drives active front end ii afe ii arfiff05 application manual ...
Page 2: ......
Page 93: ......
Page 94: ......