TROUBLESHOOTING
Service Manual M4 - M10
11.07.2002
Page
24
F1
Check parameters in groups 1 and 6
Make corrections to the settings
F1 OVER CURRENT
Parameter
settings OK
Disconnect motor cable from the drive
Start up the drive
Fault was generated by external factor. Check:
- motor
- motor cable
- features of the load
Check the current measuring circuit according to
instructions on section 7.3.2.1. Replace
defective parts as recommended in spare part
lists
Clear fault memory
F1
Start up the drive
F1
NO
YES
NO
YES
YES
NO