Table 13: M1.35 Multi-pump (Multidrive)
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.35.10
SP1 Sleep Fre-
quency Limit
0.0
320.0
Hz
0.0
1016
The drive goes to
the sleep mode
when the output
frequency stays
below this limit for
longer than is
specified by
parameter Sleep
Delay.
0 = Not used
1.35.11
SP1 Sleep Delay
0
3000
s
0
1017
The minimum
quantity of time
that the frequency
stays below the
sleep level before
the drive stops.
0 = Not used
1.35.12
SP1 Wake Up
Level
Varies
Varies
Varies
Varies
1018
The wake-up value
of the PID feedback
supervision. Wake-
up Level 1 uses the
selected process
units.
0 = Not used
1.35.13
Multi-pump
Mode
0
2
0
1785
Selects the Multi-
pump mode.
0 = Single drive
1 = Multifollower
2 = Multimaster
1.35.14
Number of
Pumps
1
8
1
1001
Total number of
motors (pumps/
fans) used in the
Multi-pump sys-
tem.
1.35.15
Pump ID Num-
ber
1
8
1
1500
The order number
of the drive in the
pump system. This
parameter is only
used in multifol-
lower or multimas-
ter modes.
VACON · 74
QUICK STARTUP GUIDE