P3.21.6.4 FLOW SWITCH MINIMUM FREQUENCY (ID 15587)
Use this parameter to set the output frequency level below which the Flow Switch
supervision is disabled.
10.22
COUNTERS
The VACON
®
AC drive has different counters based on the operation time of the drive and the
energy consumption. Some of the counters measure total values and some can be reset.
The energy counters measure the energy that is taken from the supply network. The other
counters are used to measure, for example, the operation time of the drive or the runtime of
the motor.
It is possible to monitor all the counter values from the PC, keypad or fieldbus. If you use the
keypad or the PC, you can monitor the counter values in the Diagnostics menu. If you use
fieldbus, you can read the counter values with the ID numbers. In this chapter, you find data
on these ID numbers.
10.22.1 OPERATING TIME COUNTER
It is not possible to reset the operating time counter of the control unit. The counter is in the
submenu Total counters. The value of the counter has 5 different 16-bit values. To read the
value of the counter through fieldbus, use these ID numbers.
•
ID 1754 Operating Time Counter (years)
•
ID 1755 Operating Time Counter (days)
•
ID 1756 Operating Time Counter (hours)
•
ID 1757 Operating Time Counter (minutes)
•
ID 1758 Operating Time Counter (seconds)
Example: You receive the value 1a 143d 02:21 of the operating time counter from the fieldbus.
•
ID1754: 1 (years)
•
ID1755: 143 (days)
•
ID1756: 2 (hours)
•
ID1757: 21 (minutes)
•
ID1758: 0 (seconds)
10.22.2 OPERATING TIME TRIP COUNTER
The operating time trip counter of the control unit can be reset. It is in the submenu Trip
counters. It is possible to reset the counter with the PC, the control panel, or the fieldbus.
The value of the counter has 5 different 16-bit values. To read the value of the counter
through fieldbus, use these ID numbers.
•
ID 1766 Operating Time Trip Counter (years)
•
ID 1767 Operating Time Trip Counter (days)
•
ID 1768 Operating Time Trip Counter (hours)
•
ID 1769 Operating Time Trip Counter (minutes)
•
ID 1770 Operating Time Trip Counter (seconds)
Example: You receive the value 1a 143d 02:21 of the operating time trip counter from the
fieldbus.
PARAMETER DESCRIPTIONS
VACON · 355
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/