Table 40: Start magnetisation parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.4.3.1
Start Magnetising
Current
0.00
IL
A
IH
517
0 = Disabled
P3.4.3.2
Start Magnetising
Time
0.00
600.00
s
0.00
516
Table 41: DC brake parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.4.4.1
DC Brake Current
0
IL
A
IH
507
0 = Disabled
P3.4.4.2
DC Braking Time at
Stop
0.00
600.00
s
0.00
508
0 = DC braking not
used
P3.4.4.3
Frequency to Start
DC Braking at Ramp
Stop
0.10
10.00
Hz
1.50
515
Table 42: Flux braking parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.4.5.1
Flux Braking
0
1
0
520
0 = Disabled
1 = Enabled
P3.4.5.2
Flux Braking Current
0
IL
A
IH
519
PARAMETERS MENU
VACON · 137
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/