Table 92: Pump running time counter parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.15.19.1
Set Runtime Counter
0
1
0
1673
0 = No action
1 = Set the value that is
specified by P3.15.19.2
to the runtime counter
of the selected pump.
P3.15.19.2
Set Runtime Coun-
ter: Value
0
300 000
h
0
1087
P3.15.19.3
Set Runtime Coun-
ter: Pump Selection
0
8
1
1088
0 = All Pumps
1 = Pump (1)
2 = Pump 2
3 = Pump 3
4 = Pump 4
5 = Pump 5
6 = Pump 6
7 = Pump 7
8 = Pump 8
P3.15.19.4
Pump Runtime
Alarm Limit
0
300 000
h
0
1109
0 = Not Used
P3.15.19.5
Pump Runtime Fault
Limit
0
300 000
h
0
1110
0 = Not Used
Table 93: Advanced settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.15.22.1
Staging Frequency
P3.3.1.1
320.0
Hz
320.0
15545
P3.15.22.2
De-staging Fre-
quency
0.0
P3.3.1.2
Hz
0.00
15546
PARAMETERS MENU
VACON · 179