
Table 6: M1 Quick Setup
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.18
Automatic Reset
0
1
0
731
0 = Disabled
1 = Enabled
1.19
Response to External
Fault
0
3
2
701
0 = No action
1 = Alarm
2 = Fault (Stop accord-
ing to stop mode)
3 = Fault (Stop by
coasting)
1.20
Response to AI Low
Fault
0
5
0
700
0 = No action
1 = Alarm
2 = Alarm+preset fault
frequency (P3.9.1.13)
3 = Alarm + previous
frequency
4 = Fault (stop accord-
ing to stop mode)
5 = Fault (stop by
coasting)
1.21
Remote Control
Place
0
1
0
172
The selection of the
remote control place
(start/stop).
0 = I/O control
1 = Fieldbus control
QUICK STARTUP GUIDE
VACON · 27
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
1