9 - START UP PROCEDURE
9.16 Description Of Parameters: Factory Settings
FACTORY
SETTINGS
100,
125,165
115,
150,205
P10
Heating set-point setting OT / RT (Open Therm / Room Thermostat 120V~)
00
= with Remote Control (RC) connected, temperature request is RC set-point
01
= Temperature Request is highest set point between RC and PCB
02
= Temperature request is RU setpoint. The RT enable the gas boiler operates
00
P11..P12
Manufacturer information
--
P13
Max. heating output
(0-100%)
100
80
P14
DHW max. output
(0-100%)
100
P15
Min. heating output
(0-100%)
00
P16
Maximum CH set-point (°C)
Selectable Range 20 - 80=(20°C to 80°C) 68°F to 176°F
00
= 176°F (80°C)
01
= 113°F (45°C)
00
P17
Pump overrun time in heating mode
(01-240 minutes)
03
P18
Burner ignition delay in CH mode
(00-10 minutes) - 00=10 seconds
03
P19
Manufacturer information
07
P20
Pump overrun time in DHW mode
(seconds)
30
P21
Anti-legionellosis function
00
= Disabled -
01
= Enabled
00
P22
Manufacturer information
(set “
22
” to display parameters
42
and above
)
00
P23
Maximum DHW set-point temperature
113°-140°F (45°-60°C), Default 49 = 120°F
49
P24
Manufacturer information
35
P25
No water safety device
00
P26..P31
Manufacturer information
--
P32..P41
Diagnostics (See SERVICE Instructions)
--
P44
Temperature unit setting
00
= °C
01
= °F
01
P67
OT/RT (Open Therm / Room Thermostat) selection.
0
= Plug and Play
1
= B&P
2
=OT (open therm STD)
02
The values listed below are factory defaults, there may be differences for each application.
Model
100
115
125
150
165
205
Fuel
Natural
LP
Natural
LP
Natural
LP
Natural
LP
Natural
LP
Natural
LP
P70
Ignition Fan
Speed**
Setting
35
35
38
38
44
44
RPM
3500
3500
3800
3800
4400
4400
P71*
Maximun Fan
Speed**
Setting
85
220
6150
220
105
120
225
RPM
5850
7200
40
7200
6050
5700
7250
P72
Minimum Fan
Speed**
Setting
50
55
40
40
43
45
40
RPM
1250
1300
1150
1150
1180
1200
1150
To calculate fan speeds
(P70 x 100)
(P71 x 10) + 5000
* For 165 Model: (P71 x 10) + 4500
(P72 x 10) + 750
P73
Boiler Power Selection
1
= 115
10
= 125
2
= 100
11
= 205
3
= 150
12
= 165
Default depends
on firing rate of
boiler as listed.
P74
CH mode burner ignition delay after burner off due to water temperature exceeding limit setting with an
interrupted call for heat
Range
=
0-255 seconds (0-4.25 min.)
0
P78
0-10V Input
0
= Disabled
1
= Temperature Setpoint (3V = minimum setpoint, 10V = maximum setpoint
2
= Power Setpoint (3V = minimum power, 10V = maximum power)
0
P82
4
= Disabled
3
= Enabled 0-10V DC Input
4
NOTE
:
To scroll to parameters
42
and above,
it is necessary to set
P22
to
22
before scrolling up to the parameter.
**See Tables : SECTION 12.4 - Parameters Setting For High Altitude.
240013371 REV B, [10/01/2021]
Summary of Contents for MACF-115
Page 2: ...MACF 150 ...
Page 4: ...MAHF 125 ...
Page 74: ...70 A 1 MODEL 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 75: ...71 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 76: ...72 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013371 REV B 10 01 2021 ...
Page 77: ...73 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013371 REV B 10 01 2021 ...
Page 78: ...74 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 79: ...75 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 80: ...76 NOTES 240013371 REV B 10 01 2021 ...
Page 81: ...77 NOTES 240013371 REV B 10 01 2021 ...
Page 82: ...78 NOTES 240013371 REV B 10 01 2021 ...
Page 117: ...33 MODEL 100 Heat Only 100 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 118: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 119: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 120: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Comb PN 240012875 REV C 10 01 2021 ...
Page 121: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 122: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 127: ...43 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES PN 240012875 REV C 10 01 2021 ...
Page 132: ...48 3 FAULT SOLUTION SECTIONS PN 240012875 REV C 10 01 2021 ...