30
ACCESSORIES
Flow Temp
Outside Temp
1k Ω
Note
°F
°C
80 Is Default.
For temperatures below -40°F (-40°C), maximum heating flow temperature set point no longer
increases and curves on the graph become horizontal. Boiler set point will override sensor
setpoint.
Boiler Control Panel
(CH)
Heating Water
Adjustments
Operating
Mode
Display
1. 1K Ohm (1K
Ω)
Outdoor Temperature
Sensor Kit - BD710487302V
•
Use the Outdoor Sensor (OAS) Kit with Heating Only
or Combi Boilers.
• Wire Control to boiler M2 terminal strip, terminals 4 and
5 as shown.
• Install/locate Control follow supplied instructions with
sensor kit and Installation, Operation and Maintenance
Manual (IOM).
Setting “Kt” Climate Curve:
1.
Boiler automatically recognizes OAS sensor when wired to
M2 terminal block. Display changes to show current default
“
Kt
” value (80). Note display value.
2.
When operating in CH mode, boiler setpoint is determined
by the
Kt
value selected and actual outside air
temperature. Refer to applicable °F (or °C) chart, (pg. 30)
for setpoint information.
• Select
Kt
range which will satisfy the desired boiler
delivery temperature based on outdoor temperature
range expected for your location. For example: if you
need 176°F water when the outside temperature is 20°F
and colder, select 35 for your
Kt
setting.
•
To change”default”
Kt
value on boiler control use
or
CH Heating buttons.
• Restrict the upper limit of the
Kt
curve by using Parameter
P16 to set the maximum boiler water temperature. P16
Default is 176°F.
3.
When OAS is installed, pressing
or
buttons will
no longer display boiler CH setpoint temperature. It now
displays the
Kt
value which can range from 10 to 90.
4.
When scrolling has stopped, boiler will automatically
“SAVE” value as new
Kt
default value and automatically
return to CH mode when no
Kt
adjustment activity
is sensed.
Kt
values can be changed in +/- 1 point
increments.
5.
To return, to verify or change current
Kt
“default value,
depress one of the CH setpoint adjustment buttons (once),
or
, while in any heating or standby mode. Adjust
Kt
value to obtain desired comfort level.
PN 240012875 REV. C [10/01/2021]
Summary of Contents for MACF-115
Page 2: ...MACF 150 ...
Page 4: ...MAHF 125 ...
Page 74: ...70 A 1 MODEL 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 75: ...71 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 76: ...72 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013371 REV B 10 01 2021 ...
Page 77: ...73 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013371 REV B 10 01 2021 ...
Page 78: ...74 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 79: ...75 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 80: ...76 NOTES 240013371 REV B 10 01 2021 ...
Page 81: ...77 NOTES 240013371 REV B 10 01 2021 ...
Page 82: ...78 NOTES 240013371 REV B 10 01 2021 ...
Page 117: ...33 MODEL 100 Heat Only 100 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 118: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 119: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 120: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Comb PN 240012875 REV C 10 01 2021 ...
Page 121: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 122: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 127: ...43 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES PN 240012875 REV C 10 01 2021 ...
Page 132: ...48 3 FAULT SOLUTION SECTIONS PN 240012875 REV C 10 01 2021 ...