Chapter 3: Configuration and commissioning
40
SynaG Series Installation Manual
The advanced configuration menu
Configuration options for this menu are shown in Table 25 below. More
information for each option is included in the related topic.
Note:
All configurable options included in “Basic configuration” on page 31 are
also available from the advanced configuration menu.
Table 25: The advanced configuration menu
Display Menu
Values
Operating
mode
Advanced default
configuration
Configuration presets, as
defined in “Basic default
configuration” on page 33
All
EN 54-13 supervision
ON/OFF
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavia
NBN S 21-100
NEN 2535
Custom
Panel mode
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavia
BS 5839-1 (No 2nd stage)
BS 5839-1 (2nd stage)
NBN S 21-100
NEN 2535
Custom
All
Sounder delay
(or Evacuation sounder
delay for NBN S 21-100
mode)
00 to 10 minutes
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavia
NBN S 21-100
Sounder operation during a
zone test
ON/OFF All
Sounder re-sound
ON/OFF
All
Silence sounders disabled
time
0 to 10 minutes
All
Fire routing delay
(or Warning sounder delay
for NBN S 21-100 mode)
00 to 10 minutes
EN 54-2
EN 54-2 Scandinavia
NBN S 21-100
NEN 2535
Extended fire routing delay
00 to 10 minutes
EN 54-2
EN 54-2 Scandinavia
NEN 2535
Add an expansion board
00 to 04 modules
All
Summary of Contents for Kidde AirSense SynaG Series
Page 1: ...SynaG Series Installation Manual P N 501 435003 1 10 REV 1 0 ISS 14OCT11 ...
Page 6: ...iv SynaG Series Installation Manual ...
Page 10: ...Chapter 1 Introduction 4 SynaG Series Installation Manual ...
Page 72: ...Chapter 4 Maintenance 66 SynaG Series Installation Manual ...
Page 84: ...Chapter 5 Technical specifications 78 SynaG Series Installation Manual ...
Page 96: ...Appendix A Configuration presets 90 SynaG Series Installation Manual ...
Page 100: ...Appendix B Product compliance 94 SynaG Series Installation Manual ...
Page 103: ......
Page 104: ......