Chapter 3: Configuration and commissioning
38
SynaG Series Installation Manual
Fire routing delay operation
The delay applies to the activation of fire routing (if configured) only if
all
of the
following are true:
• The delay is enabled
• The initiating device (detector or manual call point) is installed in an automatic
zone (or the initiating device is a detector installed in a mixed zone)
• The initiating device is configured in a zone with delays configured (by
default)
• A fire routing inhibit delay input is not activated (if configured)
• Any input using the
delays off
function must not be active
If the delay is not enabled, the control panel activates fire routing (if configured)
immediately after the detection of the fire alarm.
Extended fire routing delay
Use this menu to configure an extended fire routing delay of up to 10 minutes in
operating modes where the feature is available.
Default delays
The default extended fire routing delay for each operating mode is shown below.
Table 24: Extended fire routing delay default values
Operating mode
Default delay in minutes
EN 54-2 Scandinavia
03
NEN 2535
03
EN 54-2
00
EN 54-2 Evacuation
BS 5839-1
NBN S 21-100
This feature is not available in these operating modes.
To configure an extended delay:
1. Set the display as shown below, and then press Enter.
The Fire Routing Delay LED flashes fast to indicate that the fire routing delay
configuration menu is active.
2. Select a delay value from 00 to 10 minutes using the value selection buttons
(2 and 4).
This value must be greater than the configured fire routing delay.
3. Press Enter.
Summary of Contents for Kidde AirSense SynaG Series
Page 1: ...SynaG Series Installation Manual P N 501 435003 1 10 REV 1 0 ISS 14OCT11 ...
Page 6: ...iv SynaG Series Installation Manual ...
Page 10: ...Chapter 1 Introduction 4 SynaG Series Installation Manual ...
Page 72: ...Chapter 4 Maintenance 66 SynaG Series Installation Manual ...
Page 84: ...Chapter 5 Technical specifications 78 SynaG Series Installation Manual ...
Page 96: ...Appendix A Configuration presets 90 SynaG Series Installation Manual ...
Page 100: ...Appendix B Product compliance 94 SynaG Series Installation Manual ...
Page 103: ......
Page 104: ......