Chapter 3: Configuration and commissioning
34
SynaG Series Installation Manual
EN 54-13 supervision mode
Use this menu to select the zone supervision mode (EN 54-13 supervision
enabled or disabled). By default EN 54-13 zone supervision is disabled.
Note:
EN 54-13 supervision mode is not available in BS 5839-1 mode.
To configure the supervision mode:
1. Set the display as shown below, and then press Enter.
The Sounder and Fire Routing Fault/Disable/Test LEDs and all zone LEDs
flash quickly to indicate that the supervision mode configuration menu is
active.
2. Select the supervision mode using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display Description
Default setting. EN 54-13 zone supervision is disabled
and all outputs are configured as Class B.
EN 54-13 zone supervision is enabled and all outputs
are configured as Class A.
Panel mode
Use this read-only menu to view the operating mode of the control panel.
To view the operating mode:
1. Set the display as shown below, and then press Enter.
Display indications for each operating mode are shown below.
Display Operating
mode
EN 54-2
EN 54-2 Evacuation
Summary of Contents for Kidde AirSense SynaG Series
Page 1: ...SynaG Series Installation Manual P N 501 435003 1 10 REV 1 0 ISS 14OCT11 ...
Page 6: ...iv SynaG Series Installation Manual ...
Page 10: ...Chapter 1 Introduction 4 SynaG Series Installation Manual ...
Page 72: ...Chapter 4 Maintenance 66 SynaG Series Installation Manual ...
Page 84: ...Chapter 5 Technical specifications 78 SynaG Series Installation Manual ...
Page 96: ...Appendix A Configuration presets 90 SynaG Series Installation Manual ...
Page 100: ...Appendix B Product compliance 94 SynaG Series Installation Manual ...
Page 103: ......
Page 104: ......